One electrical box in the kitchen stopped working, both outlets of it. It definitely worked until the day or two before.

My little outlet tester says hot/ground reversed. I'm not 100% certain but I'm pretty sure I tested every three-prong outlet in the house (to find the ones that aren't actually grounded), and there was sure no hot/ground reversal. Which sounds like a weird condition to have, ever, plus extra-weird to spontaneously develop. I o_Oed and breakered that circuit off.

Now I ask Dear Doctor Internet (Electrical Dept.) and it sounds like that reading probably means "open neutral" and a load somewhere else on the circuit. The "backstabbed outlets" that the Doctor mentions seem to be described here.

I ♥ Doctor Internet (all her Departments), but I like a second opinion from Doctor Livejournal on electrical work. Also... if I find these are backstab, I'll probably change them all over to screwed, but I'm curious if there's also a way to debug which one went bad before opening them all -- it should be either the last *working* one in the circuit chain (if the fault's in the "outbound" neutral), or the first non-working one (if fault's in the "inbound" neutral), I believe?

Date: 2011-01-06 06:12 am (UTC)
From: [identity profile] eub.livejournal.com
Good thoughts. I did try toggling the breaker off and on. There are some earth leakage breakers (Americanised as ground fault interrupters) in the kitchen, but not on this circuit. All but the one outlet box are delivering juice, BTW.

I'm betting I'll find a continuity break in the circuit's neutral, which I can then binary search on (with the whole kitchen off, which is why I'm waiting for daylight).